How it works / Basic function
The high-frequency presence
detectors from the Control PRO
range control lighting as well as
heating, ventilation and air-con-
ditioning (COM 2 only), e.g. in of-
fices, WCs, public buildings or at
home, in relation to ambient
light level and the presence of
persons. Modern, high-frequen-
cy technology guarantees that
movement is detected absolute-
ly anywhere irrespective of radi-
ated temperature. Sensing
movement in two directions, the
DUAL HF sensor is ideal for corri-
dors in hotels, schools and office
buildings. The presence detec-
tor's switching outputs and
reach are set at the potentio-
meters and dip switches or by
means of the optional remote
control. Presence Control has
a low intrinsic power consump-
tion.
Presence Control PRO
HF 360 COM 1 / COM 1 AP
DUAL HF COM 1 / COM 1 AP
1 switching output operating
in relation to brightness setting
and presence of persons.
Settings:
- Brightness setting
- Stay-'ON' time, pulse mode,
IQ mode
Presence Control PRO
HF 360 COM 2
1 switching output, such as
COM 1. Plus a 2nd switching
output for HVAC (heating /
ventilation / air conditioning)
governed by presence.
Settings:
- Stay-'ON' time
- Switch-'ON' delay
- Room surveillance
Presence Control PRO
HF 360 DIM
DUAL HF DIM
1 switching output operating
in relation to brightness setting
and presence of persons.
Settings:
- Brightness setting
- Stay-'ON' time, IQ mode
- Orientation light
- Constant lighting control
Detection zone
The reach of the HF 360 is electronically adjustable.
1 or 2 detection directions can be masked out for
adjustment to the room situation. An angle of cov-
erage of 360° provides a max. reach of 8 m.
The DUAL HF sensor has 2 special HF sensors that
detect movement from the ceiling in both direc-
tions. Controlled electronically, reach is infinitely
variable in both directions from 3 x 3 m – 10 x 3 m.
HF 360 mounting height 2.8 m DUAL HF mounting height 2.8 m
쐽 Disconnect the power supply
before attempting any work
on the sensor!
쐽 During installation, the elec-
tric power cable to be con-
nected must be dead. There-
fore, switch 'OFF' the power
first and use a voltage tester
to make sure the wiring is off
circuit.
쐽 Installing the sensor involves
work on the mains power
supply. This work must there-
fore be carried out profes-
sionally in accordance with
the applicable national wir-
ing regulations and electrical
operating conditions (VDE
0100).
쐽 It is only permissible to use
electronic ballasts with isola-
ted control signal at the DIM
1-10 V control output.
System components
Load module
Sensor module
Sensor base
Dip switches
(1) Normal/test mode
(2) Semi-/fully automatic
mode
(3) Button/switch
(4) 'ON' / 'ON'-'OFF' button
(5) DIM option
Constant lighting control
'ON'/'OFF'
Twilight setting
Time setting
Switching output 1
HVAC stay-'ON' time
Switching output 2
HVAC switch-'ON' delay
Switching output 2
Reach setting
Clamping-type ceiling
adapter, optional
Surface-mounting adapter
IP 54, optional
Locking mechanism
Assembly/Installation
Parallel-connected
configurations
Stay-'ON' time
Orientation light
DIM option
Film shroud for minimising
the detection zone (HF 360).
Assembly/Installation (see chart on page 2)
The sensor is only intended for
concealed, indoor installation in
ceilings (apart from the COM 1
AP - surface-mounted - option).
A clamping-type ceiling adapter
or surface-mounting adapter is
not included.
Sensor and load module come
ready assembled and must be
plugged together after fitting
the load module and setting the
potentiometers/dip switches.
Accessories:
Clamping-type ceiling adapter,
EAN no.: 4007841 000370
Surface-mounting adapter,
EAN no.: 4007841 000363
Guard cage,
EAN no.: 4007841 003036
Service remote control,
EAN no.: 4007841 000387
User remote control,
EAN no.: 4007841 003012
Operating instructions
GB
Dear Customer,
Congratulation on purchasing
your new STEINEL presence de-
tector and thank you for the
confidence you have shown in
us. You have chosen a high-qual-
ity product that has been manu-
factured, tested and packed with
the greatest care.
Please familiarise yourself with
these instructions before at-
tempting to install the presence
detector because prolonged, re-
liable and trouble-free operation
will only be ensured if it is fitted
and used properly.
We hope your new STEINEL
sensor will bring you lasting
pleasure.